Dew point of moist air by the Magnus form, in degrees Celsius.
gamma = ln(RH) + a*T/(b+T), Td = b*gamma/(a - gamma), with T in degrees
Celsius and RH as a fraction. Throws an Error on a non-finite temperature
or a humidity outside (0, 1], since zero humidity has no dew point. The
coefficients are fitted over roughly -45 to 60 degC, and a temperature outside that range is not refused. The saturated identity is mathematical; floating-point evaluation has rounding error and can become nonfinite at the formula's singularities, including T = -243.12 degC.
This is the only dew-point formula in the engine; the envelope analyzer
calls it for the indoor air.
Dew point of moist air by the Magnus form, in degrees Celsius.
gamma = ln(RH) + a*T/(b+T),Td = b*gamma/(a - gamma), withTin degrees Celsius andRHas a fraction. Throws anErroron a non-finite temperature or a humidity outside(0, 1], since zero humidity has no dew point. The coefficients are fitted over roughly -45 to 60 degC, and a temperature outside that range is not refused. The saturated identity is mathematical; floating-point evaluation has rounding error and can become nonfinite at the formula's singularities, including T = -243.12 degC.This is the only dew-point formula in the engine; the envelope analyzer calls it for the indoor air.